Application
A Q335 thermocouple in conjunction with a pilot burner, provides a flame proving function in a
gas appliance.
As long as pilot burner flame is present the millivolt output from the thermocouple keeps the
safety valve in the combination gas control open, allowing main gas to flow to the aplliance
upon demand.


Specification
Output: 22 ... 30 mV
Heat-up time: 15 s max.
Drop-out time: 30 s max.

Heat- up time
The minimum open circuit output of the thermocouple shall be 15 mV within 20 s when heated
in such a way that in satbilized situation the thermocouple tip is at least 600 °C.

Drop-out time
The maximum drop--out time shall be 30 s, unless otherwise mentioned.
The open circuit output of the thermocouple shall drop below 4 mV within 30 s after removing
heat source, when thermocouple is mounted in a single port pilot burner and thermocouple tip
is heated by a gas flame up to 700 °C.

Recommended temperatures
Hot junction: 650 ± 50 °C
Cold junction: 415 °C max.

Recommended pilot burners
C7034A and Q334A ''1000 series'' for Q335A
Q334A ''2000 series'', Q349A, Q359A and Q385A for Q335C


· Table: Ordering information (packing quality 100 pieces)
Dimensions Q335A/C
EN2R-9002 0109R6-NE
Q309A
Q331A
Q335A-C
Q370A